the configured address for the connection to the module is incorrect.The controller is attempting to make a connection to the module and has received an error. the I/O module targeted does not have enough connections available.Ĭheck the number of controllers making a connection to this I/O module and verify that the number of connections is within the limits of the I/O module.the I/O memory limits of the controller are exceeded.Ĭheck the I/O memory available and make program or tag changes if needed.

powerflex 700 manual fault codes

#POWERFLEX 700 MANUAL FAULT CODES FREE#

If all of the connections are used, try to free some of the used connections or add another module to route the errant connection through.

  • there are not enough connections available either for the controller or for the communication module being used to connect through.Ĭheck the connection use of the controller or communication module.